Motor Controller 6 AC KNX DRM
30.11.2020
Ref. 5157011A
14/
26
6.1.3 Slat position closed/reversed ONLY FOR VENETIAN BLINDS
Default value:
Max. closed (100)/Max. reversed (0)
Selection options:
Max. closed (100)/Max. reversed (0)
Max. closed (0)/Max. reversed (100)
•
Max. closed (100)/Max. reversed (0)
If the value "100" is transmitted to the corresponding object (19-24, 31-36), the slats are completely closed.
If the value "0" is transmitted to the corresponding object (19-24, 31-36), the slats are reversed or completely
open.
•
Max. closed (0)/Max. reversed (100)
If the value "0" is transmitted to the corresponding object (19-24, 31-36), the slats are completely closed.
If the value "100" is transmitted to the corresponding object (19-24, 31-36), the slats are reversed or com-
pletely open.
6.1.4 Automatic cascading reduces power spikes through motors
Default value:
No
Selection options:
No
Yes
If this parameter is set to "Yes", the motor outputs move to the corresponding position with a 1 second delay.
This delay is taken into account when starting the positions, which are generated based on the
"Mains power return" settings.
H
Advantage: With large systems, power spikes are reduced.
6.1.5 Send blinds to upper end limit after download
Default value:
Yes
Selection options:
No
Yes
If this parameter is set to "Yes", a reference travel of 5 minutes to the upper end limit is conducted after
every ETS download. The reference travel can be stopped at any time.
Wert (0/100)
Wert (100/0)
Value (100/0)
Value
(0/100)
Wert (0/100)
Wert (100/0)
Value (100/0)
Value
(0/100)