Motor Controller 6 AC KNX DRM
30.11.2020
Ref. 5157011A
18/
26
6.3.1.2 IP 1 Slat position (0
–100%)
Default value:
0%
Selection options:
0
–
100%
This parameter sets the
intermediate position 1 "Slat“. The target value in % refers to the configured com-
plete slat tilts of the corresponding blind on the menu index card Motor 1…6/Motor 1–6.
6.3.2 Intermediate position 2 (IP2)
6.3.2.1 Up/Down position (0
–100%)
Default value:
0% (function disabled)
Selection options:
0
–100%
This parameter sets the intermediate position 2 "Up/Down“. The target value in % refers to the configured
travel times of the corresponding blind on the menu index card Motor 1…6/Motor 1–6.
If the Up/Down intermediate position is set to 0%, the function is disabled.
6.3.2.2 IP 2 Slat position (0
–100%)
Default value:
0%
Selection options:
0
–
100%
This parameter sets the intermediate position 2 "Slat“. The target value in % refers to the configured com-
plete slat tilts of the corresponding blind on the menu index card
Motor 1…6/Motor 1–6.
6.3.3 Security position low priority
Default value:
Ignore
Selection options:
Upper end limit
Lower end limit
Intermediate position 1 (IP 1)
Intermediate position 2 (IP 2)
Ignore
Stop
Close window
Open window
Only Up possible (ZIP screen)
Value (0%)
Wert (0%)
Wert (100%)
Value (100%)
Value (0%)
Wert (0%)
Wert (100%)
Value (100%)