Motor Controller 6 AC KNX DRM
30.11.2020
Ref. 5157011A
19/
26
This parameter sets the "Security position low priority“ for the corresponding blind. If a telegram with the
value "1" is received by one of these communication objects (objects 55-60), the corresponding blind moves
to position configured in the ETS software.
If a telegram with the value "0" is received by one of these communication objects, no operation is per-
formed. If the "Restore previous position after security" function is set to "Yes" on the "Functions motor 1...6"
menu index card, the blind returns to the position and angle it was in before this priority was enabled once
the "low priority" (value "0") has ended.
6.3.4 Security position high priority
Default value:
Upper end limit
Selection options:
Upper end limit
Lower end limit
Ignore
Close window
Open window
Stop
This parameter sets the "Security position high priority“ for the corresponding blind. If a telegram with the
value "1" is received by one of these communication objects (objects 61-66), the corresponding blind moves
to position configured in the ETS software.
If a telegram with the value "0" is received by one of these communication objects, no operation is per-
formed.
If the " Restore previous position after security " function is set to "Yes" on the "Functions motor 1...6" menu
index card, it will be checked regardless of whether the "low priority" is active or inactive. If "low priority"
(value "1") is active, the blinds move to the "Security position low priority" position (see previous point). If
"low priority" (value "0") is also active, the blinds return to the last position, with the last angle, they were in
before the high and low priority was enabled.
6.3.5 Cyclic monitor time (in minutes, 0
–255)
Default value:
0
Selection options:
0
–
255 minutes
The cyclic monitor time is active and applies to the high and low priority security objects.
The cyclic transmitter must be four times quicker than the cyclic monitoring. For example, if the cyclic mes-
sage from the transmitter is set to 1 minute, the cyclic monitor time must be set to
≥ 4 minutes.
6.3.6 Restore previous position after security
Default value:
No
Selection options:
No
Yes
The parameter setting "Yes" causes the last active run command to be repeated after the security function
has ended. This means that the blind will be moved back to the position in which it was before the receipt of
a telegram with the value "1" at one of the corresponding safety objects (low or high safety).