5 Interpreting Measured I-V Curves
5-14
Figure 53. The effect of intentionally shading entire modules in different
combinations, in two parallel-connected strings
NOTE
The graphic shown in Figure 53 is not a screen generated by the PVA-600 Software
interface.
In general, these types of patterns in the I-V curve are indications of mismatch between
different areas of the array or module under test. Although the figures shown above all
involve shading, mismatch can have other causes. The notches in the I-V curve are
indications that bypass diodes in series connected modules are activating and passing
current around the affected module(s).
Potential causes are summarized below, and then discussed in more detail.
Potential causes located in the array include:
Array is partially shaded
PV cells are damaged
Bypass diode is short-circuited