Modbus/TCP
Enable/Disable Modbus/TCP to monitor and control the I/O
ports with Modbus/TCP
Notify Input Port
Change
When its input port‟s value is changed, it sends response
data without any master‟s query.
Master/Slave
Slave: When a master request a query to read and write, it
outputs data its output port or sends its input port value
Master: Write its input port data to the remote device‟s
output ports. Reads the remote device‟s input port and
reflects it its output port.
Poll Interval
Interval to sends queries to slave when it operates as a
master
(Unit: 1ms, Resolution: 10ms)
Unit ID
Modbus/TCP Unit ID
Input Port Base
Address
Input Port Address (Reference Number)
The difference between Input Port Base Address and Output
Port Base Address should be over 8.
Out Port Base Address
Out Port Address (Reference Number)
The difference between Input Port Base Address and Output
Port Base Address should be over 8.
Passive Connection
Operates as a TCP server for Modbus/TCP
Active Connection
Operates as a TCP client for Modbus/TCP
Peer Address
A host name or IP address to make a TCP connection for
Modbus/TCP
Peer Port
Passive Connection: TCP port number to listen to
Active Connection: TCP port of the remote host to make a
TCP connection
Table 5-6 ezManager I/O Port – Basic Settings Tab
I/O Port – I/O Port Option
Digital Input
Valid Time
The input signal should keep during the Valid Time to
recognize it. (Unit: 1ms, Resolution: 10ms)
Digital Output
Macro
Enable/Disable the Macro function
Do0 ~ Do7
Equations for macro function