CIE-M10 User’s Manual Ver. 1.1
Sollae Systems Co., Ltd.
- 33 -
http://www. eztcp.com
interval. (Unit: ms, minimum value: 10)
Unit ID
Slave: CIE-M10‟s unit ID
Master: Slave‟s unit ID
Input Port Base Address
Slave: CIE-M10‟s input port address
Master: Slave‟s input port address
Output Port Base Address
Slave: CIE-M10‟s output port address
Master: Slave‟s output port address
The difference between Input Port Base Address and Output Port Base Address
should be over 8.
Passive Connection / Active Connection
This field is for specifying TCP connection method. The passive connection is a standard
of Modbus/TCP. The CIE-M10 waits for a TCP connection from the master if the passive
connection is selected.
CIE-M10 also has an active TCP connection function to make a TCP connection to remote
Modbus/TCP device.
Peer Address
When CIE-M10 makes an active TCP connection, Peer Address is the destination address
to connect.
Port
Passive Connection: A port number to wait for a TCP connection from remote host.
Active Connection: A port number to make a TCP connection to remote host
7.2.5
Mater Mode
A master outputs data after reading remote device‟s input ports and write to the remote
device‟s output ports after reading its input ports. User can make a remote switch system with
this mode.
7.2.6
Serialized Modbus/TCP
CIE-M10‟s I/O port can be accessed through the serial port with Modbus/TCP. The data is as
same as data over TCP of Modbus/TCP.