Electrical Connections
Electrical Connections
Grid Cable and Micro-breaker recommended
Figure: Wrong connection of load and inverter
Cable (copper)
Micro-Breaker
Model
X1-Hybrid-3.0-D X1-Hybrid-3.7-D X1-Hybrid-5.0-D X1-Hybrid-6.0-D
4-6 mm
²
6-8 mm
²
4-6 mm
²
4-6 mm
²
50 A
Ø
Grid port connection
EPS(Off-grid) Cable and Micro-breaker recommended
Cable (copper)
Micro-Breaker
Model
X1-Hybrid-3.0-D
X1-Hybrid-3.0-M
X1-Hybrid-3.7-D
X1-Hybrid-3.7-M
X1-Hybrid-5.0-D
X1-Hybrid-5.0-M
X1-Hybrid-6.0-D
X1-Hybrid-6.0-M
3-4 mm
²
3-4 mm
²
8-10 mm
²
8-10 mm
²
25 A
25 A
32 A
32 A
50 A
40 A
32 A
X1-Hybrid-7.5-D
6-8 mm
²
50 A
X1-Hybrid-7.5-D
X1-Hybrid-7.5-M
8-10 mm
²
40 A
5.2 Grid Port and EPS(Off-grid) Output Connection
X1-Hybrid-3.0-M X1-Hybrid-3.7-M X1-Hybrid-5.0-M X1-Hybrid-6.0-M X1-Hybrid-7.5-M
4-6 mm
²
4-6 mm
²
Cable (copper)
Micro-Breaker
3-4 mm
²
3-4 mm
²
25 A
25 A
32 A
32 A
6-8 mm
²
40 A
Model
PV1+
PV2+
PV1-
PV2-
Schematic diagram of the inverter PV connected.
36
37
Don gle/U pgrade
Dongle/ Upgr ade
X1-Hybrid G4 series inverter are single-phase inverter. Suitable for rated
voltage 220/230/240 V, frequency 50/60 Hz. For more technical
requirements, please consult the requirements of the local public grid.
The circuit breaker should be installed between the inverter and the
mains, and the load should not be directly connected to the inverter.
The following is the location of the inverter positive and negative
(PV-/PV+) ports.