Setting
p) DRM function (applied to NZS4777.2)
>Function Control
DRM Function
Enable
q) Main Breaker Limit
>Current
40A
Main Breaker Limit
>Proportion
Power Limit
1.00
n) Power limit
Power limit function, the maximum power of the AC port can be set
m) FVRT Function(apply to 50549)
Here you can enable or disable the FVRT Function.
Function Control
Disable/Enable
FVRT Function
98
For power limit of smart meter or CT, the current must be set in line with
the utility's contract requirements. In case of failure to set, it may cause a
circuit breaker fault of main switchboard, adversely affecting the
charging or discharging of battery.
Click Main Breaker Limit to enter the setting interface, and then choose
the corresponding amperage according to the utility's requirements.
o) AS4777 Setting
It is the same as the function of Export Control, but it’s only applicable to
Australia and New Zealand.
Here you can set the high and low enable or disable.
The DRM function is a demand response method required by the
NZS4777.2 standard and is only applicable to NZS4777.2.
The default value is "enable". Select "Disable" to disable this function.
>
Export
Control
G
eneral
Control
AS 4777 Setting
Soft Limit
Enable
Disable
Export Control
Soft Limit
Value
7500 W
Export Control
Hard Limit
Enable
Disable
Export Control
Hard Limit
Value
7500 W
Export Control
Export
Control
>
G
eneral
Control
AS 4777 Setting
Soft Limit
Enable
Disable
General Control
Soft Limit
Value
7500 VA
General Control
Hard Limit
Enable
Disable
General Control
Hard Limit
Value
7500 VA
General Control
r) Battery Heating
>Func Select:
Enable/Disable
Battery Heating
>Heating Period 1
Start Time
00:00
Battery Heating
>Heating Period 1
End Time
00:00
Battery Heating
>Heating Period 2
Start Time
00:00
Battery Heating
>Heating Period 2
End Time
00:00
Battery Heating
If the battery heating function is needed, you can set it to turn on here,
and set the time period that needs to be heated, and two time periods
can be set. The function will be triggered automatically within the set period(s).
(Only for batteries with heating function.)