Setting
Setting
(4) Power Factor
Func Select
OFF
SPF & Q(V)
>
Func Select: OFF, Q (V), SPF and Response Time; the Q (V) can set the value of Q1
(V1) or
Q4 (V4), the SPF can set PF Value and the Response Time can
be set
.
Specified power factor (SPF) means that the inverter operates at a specified, non-
unity power factor. PF Value can set the value of “ind” or “cap”. The range is 80% to
100% (80 means 0.8).
Response Time: range is 1.0s to 90.0s, the default is 10.0s.
Volt-Var mode means that the inverter supplies or absorbs reactive power as a
function of voltage.
Q
1
(CAP)
Q
2
= Q
3
= 0
V
1
V
nom
V
2
V
3
V
4
Q
4
(IND)
Q2
Q1
0% ~ 100%
(0%KVA~45%KVA)
Q3
Q4
V1
82.0% ~ 103.0%
-100.0% ~ 100.0%
V2
92.0% ~ 105.0%
95.0% ~ 108.0%
V3
-100.0% ~ 0.0%
97.0% ~ 118.0%
V4
(3) RR
> Func Select
OFF
Ramp Rate
Func Select: OFF or ON can be chosen; Ramp-up rates for inverter is to help
smoothen the transitions from one output level to another output level.
Norm Ramp Rate: range is 1.0% to 100.0%.
SSRamp Rate: range is 2.0% to 100.0% (RULE21) or 0.1% to 100% (RULE 14H),
the default is 2.0%.
(1) L/HVRT
Hv2
121.0V
L/HVRT
Operating parameters that correspond to Rule21 or PUERTO RICO or
Rule 14H voltage ride-through and must trip regions are shown in the
table.
(2) L/HFRT
>HF2
60.10HZ
L/HFRT
Voltage at PCC
(% Nominal Voltage)
Region
High Voltage2 (Hv2)
Default Setting
Adjustable Range
Ride Through
Until
Operating Mode
Maximum
Trip Time(s)
Range of Adjustable
Voltage at PCC (%
Nominal Voltage)
Range of Adjustable
Maximum Trip Time
(s)
High Voltage1 (Hv1)
Near Nominal (NN)
Low Voltage1(Lv1)
Low Voltage2 (Lv2)
Low Voltage3 (Lv3)
V ≥ 120
110<V≤120
88 ≤ V ≤ 110
70 ≤ V ≤ 88
50 ≤ V≤70
V<50
NA
12 sec
Indefinite
20 sec
10 sec
1 sec
Not Applicable
Momentary Cessation
Mandatory Cessation
C o n t i n u o u s
Mandatory Operation
Mandatory Operation
0.16 sec
13 sec
Not Applicable
21 sec
11 sec
1.5 sec
101-120
NA
45-99
101-120
45-99
45-99
NA
NA
1-60
1-60
1-60
1-60 (14H: 0.5-60)
Operating parameters that correspond to Rule21 or PUERTO RICO or
Rule 14H Frequency ride-through and must trip regions are shown in the
table.
System Frequency
Default Setting(Hz)
Region
High Frequency2 (HF2)
Default Setting
Adjustable Range
Ride Through
Until (s)
Ride-Through
Operatinal Mode
Trip Time(s)
Range of Adjustability
Frequency (Hz)
Range of Adjustable
Trip Time (s)
High Frequency1 (HF1)
Near Nominal (NN)
Low Frequency1 (LF 1)
Low Frequency2 (LF 2)
f>62
60.5≤f ≤ 62
58.5 ≤ f ≤ 60.5
57.0 ≤ f≤58.5
f ≤ 57
.
0
No Ride-Through
299
Indefinite
Not Applicable
ContinuousOperation
M a n d a t o r y
Mandatory Operation
0.16
300
Not Applicable
300
0.16
60.1-66
NA
53-59.9
60.1-66
53-59.9
0.16-1000
NA
1.0-1000
1.0-1000
0.16-1000
299
No Ride-Through
Not Applicable
-100.0% ~ 100.0%
62
63