![Solas TWENTY6 ST-26N Скачать руководство пользователя страница 32](http://html1.mh-extra.com/html/solas/twenty6-st-26n/twenty6-st-26n_installation-and-operation-manual_1314191032.webp)
SÓLAS
CONTEMPORARY FIRE
32
ASSEMBLY & INSTALLATION
Gas Supply Line
Once the vent pass-through (or pass-throughs) are
finished, the gas supply line should be installed. The
supply line should exit the wall that the fireplace will be
installed on at the location specified on the installation
template We suggest the installation of a shut-off valve in
the supply line between the wall and the connection to
the fireplace. Your professional gas installer or local gas
company will determine the specific requirements for the
gas supply line as the requirements may vary in different
locations. In every case, the installation must conform
with local codes or, in the absence of local codes, with
the National Fuel Gas Code, ANSI Z223.1 or the Canadian
Installation Code, CAN/CGA B149.
Gas Connection
1. Verify that the gas type is correct for the fireplace by
looking at the rating plate that is attached to the right
side of the fireplace, adjacent to the control battery
pack.
Note: The fireplace is shipped from the factory
equipped to burn the fuel listed on the rating plate.
Conversion kit information and instructions are
available on page 49.
2. The gas connection should now be made from the
gas supply line to the inlet on the fireplace. Use only a
licensed gas installer to make the connection.
3. The fireplace is shipped from the factory with a 3/8" tube
OD (male) flare connection.
4. The gas supply piping should have a separate gas
shut-off valve and a 1/8" NPT plugged tapping upstream
of the valve. We recommend installing a shut-off valve
between the gas supply line where it penetrates
the wall / fireplace mounting plate and the inlet to
the regulator on the fireplace. This will allow gas to
be shut-off to the fireplace by simply removing the
fireplace sur-round to gain access to the shut-off valve.
NOTE: The fireplace and its main burner valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psi (3.5kPa).
NOTE: The fireplace must be isolated from the gas
supply piping system by closing the gas shut-off valve
during any pressure testing of the gas supply system at
test pressures equal to or less than 1/2 psi (3.5kPa). After
the gas supply has been connected, use a commercial
gas leak detector or apply a soapy water solution to all
the fittings to check for gas leaks. Never use a flame to
test for leaks.
Gas Shut-Off