6.2.6 Laying battens 2; 3; 4; 5
These battens are to be arranged and fastened according
to the measurement and tolerance information in Figure
3 on page 10 (or also in Table 1 on page 11).
6.2.7 Laying batten 6: Aluminum guide rail
40x40 on the fastening plate
The fi rst aluminum guide rail must be laid with a spacing
of 1.642 mm to the top edge of the supporting board 98
x 20. Here it is essential that the tolerance requirement
+/- 5 mm be observed because the aluminum guide rail is
also used as a measurement reference point for the mod-
ule row laid out above (see Figure 3).
The aluminum guide rails are fi xed with fastening plates
which are fastened centrally to the counter battens with
wood screws 6 x 60.
Figure 14
Aluminum guide r
ail
Fastening plate
NOTE
You must fi rst push the required number of fastening plates onto the aluminum guide rail before you start fas-
tening the counter batten!