Error # Single Phase
Error # Three Phase
LCD
Message
Cause and Troubleshooting
CPU v3.18
and below
CPU v3.19
and above
CPU v3.18
and below
CPU v3.19
and above
5. Connect each DC string separately, turn the AC and the inverter ON/OFF switch to
ON, until the error appears for the faulty string.
o
Do not connect strings with a grounding fault to the inverter. A certified installer must
fix the faulty string before connecting it to the inverter
o
For further documentation, contact SolarEdge Support.
14
2xE
58/59/60
8x19/ 8x1A/
8x1B
AC Voltage Too
High (Line 1/2/3)
If the fault persists:
o
Check the AC connection to inverter.
o
Verify that the inverter is set to the correct country.
o
Check with the grid operator if a large surge source or irregular load exists near the
site.
o
Verify that the output wire size matches the distance between the inverter and the
location of the grid connection.
o
Use a larger gauge wire for the AC output.
o
Refer to the
AC Wiring Application Note
http://www.solaredge.com/files/pdfs/application-note-
recommended-wiring.pdf
15
2xF
85, 86, 88,
8x34, 8x35,
8x37
DC Voltage Too
High (surge)
The SolarEdge system normally eliminates DC overvoltage errors. If the fault persists:
o
Turn OFF the inverter ON/OFF switch. If after five minutes, the LCD panel does not
show a low safety voltage (1V per optimizer), check which string is malfunctioning
and recheck its connections to the inverter.
o
Power Optimizer Troubleshooting
o
Re-commission all inverters in the site, as described in
16, 149,
153, 181
2x10, 2x95,
2x59, 2xB5
8x3E, 8x49,
Hardware Error
Contact SolarEdge Support.
General Inverter Error Codes
SolarEdge
-
StorEdge
-Single
Battery/High
Capacity
Installation
MAN-01-00283-1.
1
90