Chapter 6: Commissioning the Installation
This chapter describes how to activate the system, pair the power optimizers to the inverter and verify
the proper functioning of the system.
Removing the Inverter Cover
Use the following procedure for cover removal for communication connection or maintenance.
1. Turn OFF, or verify that the inverter ON/OFF switch is OFF.
2. Verify that AC to the inverter is OFF, or disconnect the AC to the inverter by turning OFF the circuit
breakers on the distribution panel. Wait 5 minutes for the capacitors to discharge.
3. Open the inverter cover’s six Allen screws and carefully pull the cover horizontally before lowering it.
CAUTION!
When removing the cover, make sure not to damage internal components. SolarEdge will not be
held responsible for any components damaged as a result of incautious cover removal.