System Warnings
Warnings are displayed in the initial status screen with the format: <Warning X>. For example:
V a c [ V ] V d c [ V ] P a c [ W ]
1 . 0 0 . 5
0 . 0
P _ O K : X X X / Y Y Y < S _ O K >
W a r n i n g 8
O N
The warning is a status screen. To view the warning description, press the LCD button.
The following is a list of system warnings:
Warning #
LCD text
Comments and troubleshooting
CPU v3.18 and
below
CPU v3.19 and
above
1-4, 6-7
8x66 - 8x69
8x6A - 8x6F
Fan # Failure
Clean or replace the fan
5
Turn Switch Off to Configure
Appears when trying to access the Setup menus during
production
8
2x111
Connection Unit Low 9V Battery
Replace the 9V battery in the StorEdge Connection Unit.
Refer to
SolarEdge
-
StorEdge
-Single
Battery/High
Capacity
Installation
MAN-01-00283-1.
1
97
System Warnings