![SolarEdge RESU10H Prime Series Скачать руководство пользователя страница 41](http://html1.mh-extra.com/html/solaredge/resu10h-prime-series/resu10h-prime-series_installation-manual_1313714041.webp)
4. If required, ground the conduit by connecting it to the grounding bar, as shown
above.
Connecting the Inverter to AC Grid
For connecting the inverter to AC grid, use a 14–4 AWG cable.
For more wiring information, refer to the
SolarEdge Recommended AC
Wiring Application Note, available on the SolarEdge website at
http://www.solaredge.com/files/pdfs/application-note-recommended-
To connect to AC grid:
1. Turn off the AC circuit breaker on the distribution panel.
2. Strip 2.5'' / 60 mm of the external cable insulation and strip 0.6'' / 15 mm of the
internal wire insulation.
Figure 13: Insulation Stripping – AC Cable
3. Pass the AC cable through the conduit.
4. Connect the wires to the AC terminals as shown below.
Figure 14: AC connection
Connecting the DC Strings to the Inverter
Connect the string to the DC input pairs. If required, connect additional strings in
parallel using an external combiner box/branch cables before connecting to the
inverter.
Single Phase Energy Hub Inverter with Prism Technology MAN-01-00842-1.3
40
Connecting the Inverter to AC Grid
Содержание RESU10H Prime Series