Troubleshooting
33
Using the configuration program, the user may specify the number of S4K288BAT external battery cabinets
attached to the UPS. The factory default is programmed for internal batteries only.
Table 6
shows estimated run times at different loads.
Table 6
Battery Run Times
Battery/External Cabinets
Load%
10000va Run Time In
Minutes
Internal Battery
10%
107
20%
52
30%
31
40%
22
50%
16
60%
13
70%
10
80%
9
90%
7
100%
6
Internal 1 External
Battery Cabinet
10%
251
20%
118
30%
74
40%
52
50%
39
60%
32
70%
26
80%
22
90%
19
100%
17
Internal 2 External
BatteryCabinets
10%
333
20%
216
30%
118
40%
85
50%
66
60%
53
70%
44
80%
38
90%
32
100%
28
Internal 3 External
BatteryCabinets
10%
494
20%
265
30%
191
40%
119
50%
92
60%
75
70%
62
80%
54
90%
47
100%
41
Internal 4 External
BatteryCabinets
10%
590
20%
295
30%
236
40%
178
50%
119
60%
98
70%
82
80%
71
90%
61
100%
54
Содержание S4K6U10000
Страница 1: ...S S4K6U10000 power availability On Line UPS 120 208V 120 240V USER MANUAL...
Страница 2: ......
Страница 46: ......
Страница 47: ......