Table 7
UPS Specifications
Specifications
14.0 S
pecificationS
Model Number
S4K6U10000
Model Rating
8000W/8660VA at 127/220 (120 or 240 degrees only)
8000W/8660VA at 120/208 (120 or 240 degrees)
8000W/10000VA at 120/240 (180 degrees)
8000W/10000VA at 115/230 (180 degrees only)
7200W/9000VA at 110/220 (180 degrees only)
6400W/8000VA at 100/200 (180 degrees only)
DIMENSIONS in (mm)
Unit W x D x H in. (mm)
10.5 x 29 x 16.93 (267 x 737 x 430)
Shipping W x D x H in. (mm)
16.5 x 34.3 x 22.8 (420 x 870 x 580)
WEIGhT lbs (kg)
Unit
109 (49.3)
Shipping
118 (53.6)
INpUT aC paRaMETERS
Nominal Operating Frequency
50 or 60 Hz (Factory Default = 60)
Factory Default VAC
120/208 VAC at 120 degrees
L1-L2 Factory Default Input Phase Angle
120 degrees
Allowable Input Phase Angle
120, 180, 240 degrees, Auto-sensing on application of AC
(Restrictions for L-N voltages other than 120 VAC)
Factory Default L1-N, L2-N VAC
120 VAC nominal
User Configurable L1-N, L2-N VAC 100/110/115/120/127 VAC (May be modified using configuration program)
L1-N, L2-N, Operating voltage Range Without Battery Operation (Except 100 vaC L-N Operation)
100% - 90% loading
90 VAC - 140 VAC
90% - 70% loading
80 VAC - 140 VAC
70% - 30% loading
70 VAC - 140 VAC
30% - 0% loading
60 VAC - 140 VAC
L1-N, L2-N, Operating voltage Range Without Battery Operation (100 vaC L-N Operation)
100% - 70% loading
80 VAC - 140 VAC
70% - 30% loading
70 VAC - 140 VAC
30% - 0% loading
60 VAC - 140 VAC
L1-N, L2-N Max. Allowable VAC
150 VAC
Input Frequency w/o Battery Operation
40 - 70 Hz
Input Power Connection
Hardwire Terminal Block 3W + G (L-L-N-G)
OUTpUT aC paRaMETERS
Factory Default VAC
120/208 VAC @ 120 degrees
L1-L2 Factory Default
Output Phase Angle
120 degrees
Allowable Output Phase Angle
120, 180, 240 degrees Auto-sensing on initial application of input AC
Factory Default L1-N, L2-N VAC
120 VAC nominal
User Configurable L1-N, L2-N VAC
100/110/115/120/127 VAC, ±3%
Output Connections
Hardwire Terminal Block 3W + G (L-L-N-G); also see
7.2- Output Receptacle Distribution Options
Frequency
50 Hz or 60 Hz, Nominal
Waveform
Sinewave
Main Mode Overload
200% for 8 cycles then shutdown; 130% for 60 seconds with transfer
to bypass
BYpaSS pROTECTION LIMITS
Disable Bypass operation
If input voltage exceeds ±15% of the nominal voltage
Re-enable Bypass operation
If input voltage returns to within ±10% of nominal output voltage
Disable Bypass operation
When the input frequency prevents synchronous operation
35