The S4K6U10000 requires very little maintenance. The batteries are valve-regulated, non-spillable, flame
retardant, lead acid and should be kept charged to obtain their design life. The UPS continuously charges the
batteries when connected to the utility supply.
When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours every four to
six months to ensure full recharge of the batteries. Failure to recharge the batteries periodically will permanently
degrade battery capacity.
The S4K6U10000 is designed to allow the user to safely replace the internal batteries. Read the safety
cautions before proceeding. Contact your local distributor or Sola/Hevi-Duty representative to obtain the
appropriate replacement battery kit part number and pricing.
12.1 Battery Replacement
Maintenance
12.0 m
aintenance
12.1.1 Internal Battery Replacement
procedures
Both battery packs should be replaced at the same time.
1. Gently remove the front bezel by unscrewing the side
mounted screws.
2. Loosen the three screws on the front battery cover grille.
Lay the battery cover grille aside for reassembly.
3. Remove the battery brackets at the bottom front of the
battery pack.
4. Grasp each battery pack assembly individually and pull
each out of the front of the UPS. Be prepared to support
the weight of the battery as it is withdrawn.
5. Unpack the new battery assemblies taking care not to
destroy the packing. Compare new and old battery
assemblies to make sure they are the same. If so, proceed
with the next step. If they are different, STOP and contact
your local distributor, Sola/Hevi-Duty representative or the
Sola/Hevi-Duty Technical Support Group.
6. Line up and slide in the new replacement battery packs.
7. Reinstall the brackets on the front of the battery pack.
8. Reconnect the slotted battery cable connectors.
9. Reattach the front battery door, tightening the three screws.
10.Reattach the front metal bezel to the UPS.
NOTE
These are hot-swappable replacement batteries. However, caution should be exercised because during this
procedure the load is unprotected from disturbances and power outages.
CaUTION
A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed before replacing the batteries:
• Remove rings, watches and other metal objects.
• Use a Phillips (crosshead) screwdriver with insulated grips.
• Do not lay tools or other metal objects on top of the batteries.
• If the battery replacement kit is damaged in any way or shows signs of leakage, contact your
local distributor or Sola/Hevi-Duty representative immediately.
• Do not dispose of batteries in a fire. The batteries may explode.
27
!
UPStatT
!
UPStation GXT
Battery
Battery Cover
Front Bezel
Battery Bracket
!
S4K Industrial UPS
!
- +
AC INPUT BATTERY UPS ON
BYPASS
L1
L2
Содержание S4K6U10000
Страница 1: ...S S4K6U10000 power availability On Line UPS 120 208V 120 240V USER MANUAL...
Страница 2: ......
Страница 46: ......
Страница 47: ......