COMMISSIONING THE INVERTER
88
HYD 5K...20KTL-3PH
Battery Address: 00 for the 1
st
battery, 01 for the 2
nd
battery etc.
The
default operating mode is the Self-use Mode.
EPS Mode, Unbalanced Support, Anti-Reflux Mode, IV-Curve Scan
and Logic interface are disabled.
6.4.1
Configuring the battery setup
The HYD 5 ... 8KTL-3PH models have one battery input (max. current
25 A). The HYD 10 ... 20KTL-3PH models have two battery inputs
(max. current 25 A / 25 A).
Battery inputs can be connected and set in parallel mode to reach 50
A / 70 A.
6.4.2
Configuring Parallel Inverter System
To increase the system's EPS and grid power, the HYD 5 ... 20KTL-
3PH can be parallelly connected at the Grid port and the EPS port.
For the communication setup, please follow the following steps:
1)
Set the Master unit
2)
Set the Slave units