ELECTRICAL CONNECTIONS
HYD 5K...20KTL-3PH
63
NOTE
•
The arrows on the current
transformers direct to the grid.
•
Up to 200 A measurement
Energy Meter Configuration
The energy meter is preconfigured to be used with the inverter with
these settings:
Modbus Address: 1
Baud Rate: 9600
Current Ratio: 40:1
Energy Meter direct connection (System C)
The energy meter type Chint DTSU666 (5/80A) must be purchased
separately, it is not included in the delivery.
Max. current input: 80 A