NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
54
EN
Output
Setup Items
Selectable Value
Default
Output Phase
1-phase
1-phase
Output Voltage
200V, 208V, 220V,
230V, 240V
230V
Output Frequency
Auto*
1
/ Converter-50Hz*
2
/
Converter-60Hz*
2
Auto
Output Sync.
Freq. Range
±0.5/ 1/ 3/ 5Hz
±3Hz
Output Freq.
Slew Rate
0.5 / 1 / 2Hz/sec.
1 Hz/sec.
Output Mode
Industrial/ IT
IT
Standby Mode
No output/ Bypass output
No output
Overload Alarm
30-105% (per step: 5%)
105%
*
1
: When the
Output Frequency
is set as
Auto
, the output frequency will
vary according to the bypass frequency. If the bypass frequency is ≥ 55Hz,
the
Free_Run_Frequency/ Cold_Start_Frequency
will be set as
60Hz
.
If the bypass frequency is < 55Hz, the
Free_Run_Frequency/ Cold_Start_
Frequency
will be set as
50Hz
.
When the
Output Frequency
is set as
Auto
and the
Bypass Output
under the
Standby Mode
item is set as
Enable
, the bypass output range
will be the same as the Output Sync. Freq. Range.
*
2
: When the
Output Frequency
is set as
Converter-50Hz/ Converter-
60Hz
, the UPS will enter the Frequency Conversion mode and the bypass
output will become
Disable
.
Input
Setup Item
Selectable Value
Default Value
Bypass Max. Voltage
+10/ 15/ 20%
+15%
Bypass Min. Voltage
-10/ 15/ 20/ 25/ 30/ 35/ 40%
-20%