NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
96
EN
Error
Code
Alarm
Message
Possible
Cause
Solution
0X8106
INV IGBT Over
Heat Shutdown
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. Check whether
the vents are
blocked.
2. Contact service
personnel.
0X6100
PFC Over Heat
Shutdown
1. The vents are
blocked.
2. The UPS has an
internal fault.
1. Check whether
the vents are
blocked.
2. Contact service
personnel.
0X1003
Battery
Disconnected
1. The UPS is not
properly connected
to the external battery
pack(s).
2. The battery/ batter-
ies is (are) damaged.
1. Check whether
the UPS is properly
connected to the ex-
ternal battery pack(s).
2. Contact service
personnel.
If all possible causes are eliminated but the alarm still appears, please
contact your local vendor or customer service.
3. Error code on display and event list.
Error Code
Alarm Message
0x0100
Mains Input Volt Out Range
0x0120
Mains Input Freq Out Range
0x0121
Input relay short
0x0122
Input Fuse Open
0x0277
Bypass relay Fault
0x02B0
Bypass Over Current
0x1001
Battery End Of Discharge
0x1002
Battery Over Charged
0x1003
Battery Disconnected
0x1004
Battery Life time Expired
0x1005
Battery Reversed
0x1012
Battery Test Fail
0x1013
Battery Test In Progress
0x1030
Li-ion Battery Over Volt Warning
0x1031
Li-ion Battery Under Volt Warning