Battery/ Battery Pack Connection Warnings
- Only use the same type of batteries from the same supplier. Never use old, new
and different Ah batteries at the same time.
- The number of batteries must meet UPS requirements.
- Do not connect the batteries in reverse.
- Use the voltage meter to measure whether the total voltage, after battery pack
connection, is around 12.5Vdc × the total number of batteries.
Before commencing any operation, make certain that:
• the UPS has been shut down completely and all isolation switches are OFF;
• switches upstream of the UPS are OFF.
• Set the switch on the back of the battery extension module to the OFF position.
• Connect the battery extension module to the UPS.
• Set the switch on the back of the battery extension module to the ON position.
• Set the number of EBM connected to the UPS in the Settings menu.
Turn off the UPS and cut off the AC source before performing battery/
battery pack replacement.
A battery can present a risk of electric shock and high short-circuit current.
Servicing of batteries and battery packs must be performed or supervised
by qualified service personnel familiar with batteries, battery packs and the
required precautions. Keep unauthorized personnel away from batteries
and battery packs.