Press and hold the button
for 3 seconds
and release it after you hear one beep.
In Progress...
Self Diagnosis
BYPS
231
V
PS
INV
4 Once the UPS is running normally, switch on the output protective devices (see
Figure 7-3
) installed between the UPS and the loads.
8.1.2. Start-up with Batteries (Single Unit)
1 Please check the '+' and '-' poles of the batteries and ensure that wiring is correct.
2 Turn on the UPS’s external battery pack’s breaker.
3 When there is no AC input, press and hold the ON/ OFF button ( ) for 3
seconds to start up the UPS. Release the button after you hear one beep and
the UPS will start up. After the UPS performs self-diagnosis, the UPS will run in
BATTERY mode.