NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
83
EN
16
Once the maintenance is completed, re-install UPS1, UPS2 and the external
battery pack(s).
17
Reconnect all of the battery cables, power cables and communication cables.
18
Turn on the circuit breaker on each connected external battery pack.
19
Turn on the UPS1’s INPUT BREAKER.
20
Turn on the UPS2’s INPUT BREAKER.
21
Turn on the Manual Bypass’ UPS-1 OUTPUT BREAKER.
22
Turn on the Manual Bypass’ UPS-2 OUTPUT BREAKER.
23
Switch the Manual Bypass’ BYPASS BREAKER to the OFF position. The ON/
OFF printing is marked on the BYPASS BREAKER (see
Figure 10-21
).
TO UPS PARALLEL
TO UPS PARALLEL
N
(L
2)
L(L
1)
N
(L
2)
L(L
1)
BYPASS MODE
UPS MODE
UPS-2
UPS-1
OUTPUT BREAKER
BYPASS BREAKER
Bypass Breaker
OFF
ON
TO UPS-1 INPUT
TO UPS-2 OUTPUT
TO UPS-2 INPUT
N
L
N
INPUT
OUTPUT
(Figure 10-21)
24
Re-install the cover plate of the BYPASS BREAKER on the Manual Bypass.
This will automatically inactivate the manual bypass detector.
25
Press and hold the UPS1’s ON/ OFF button for 3 seconds and release it after
you hear one beep to turn the UPS1 on.
26
Press and hold the UPS2’s ON/ OFF button for 3 seconds and release it after
you hear one beep to turn the UPS2 on.
27
The UPS system is ready for normal operation. Please refer to the UPS User
Manual for more information.
If you encounter any problems that you cannot solve, please ask your local
vendor or customer service for more information. Do not attempt to solve
the problems if you are not trained for it.