NETYS RT 5 - 7 - 9 - 11 kVA - 551570A - SOCOMEC
73
EN
NRT3-OP-PMB
TO UPS PARALLEL
TO UPS PARALLEL
TO UPS-1 OUTPUT
BYPASS MODE
UPS MODE
UPS-2
UPS-1
OUTPUT BREAKER
BYPASS BREAKER
WARNING:
ONLY AUTHORIZED SERVICE PERSONNEL
CAN REMOVE THIS COVER PLATE.
REMOVING THIS COVER PLATE WILL CAUSE
THE INVERTER TO SHUTDOWN. SEE THE
USERS MANUAL FOR INSTRUCTIONS.
1
4 5
2
6
7
9
10
10
3
8
TO UPS-1 INPUT
TO UPS-2 OUTPUT
TO UPS-2 INPUT
NOTE :
Remove the terminal
cover plate and you will
see the wiring terminal
blocks.
N(L2)
OUTPUT
AC INPUT
N(L2)
L(L1)
L(L1)
N
L
N
L
N
L
N
L
INPUT
OUTPUT
No.
Item (Printed Words on
the Front Panel)
Connection
1
AC Input
Connects to the main AC utility.
2
Output
Connects to the critical loads.
3
Bypass Breaker
No connection is needed. After you remove the two
screws shown in
Figure 15
to remove the cover
plate, the PMB’s detector will automatically activate
and send a message to the UPS to ask it to transfer
into bypass mode.
4
UPS-1 Output Breaker
No connection is needed. The function is to prevent the
output terminals from damage caused by overload.
5
UPS-2 Output Breaker
No connection is needed. The function is to prevent the
output terminals from damage caused by overload.
6
To UPS-2 Output (L/ N/ )
Connects to the UPS2’s UPS Output terminals (L/ N/ )
7
To UPS-2 Input (L/ N/ ) Connects to the UPS2’s AC Input terminals (L/ N/
)
8
To UPS-1 Input (L/ N/ ) Connects to the UPS1’s AC Input terminals (L/ N/
)
9
To UPS-1 Output (L/ N/ ) Connects to the UPS1’s UPS OUTPUT terminals (L/ N/ )
10
To UPS Parallel
Connects to the UPS’s parallel port.
Содержание NETYS RT 1100 VA
Страница 1: ...5000 7000 9000 11000 VA NETYS RT INSTALLATION AND OPERATING MANUAL EN www socomec com netys manuals ...
Страница 2: ......
Страница 103: ......