13
Photo 29
Photo 30
15
14
Run a wire from the terminal block where
the solenoid valve was connected to one
of the pins on the delay timer
(Item 14)
with one of the female disconnects
(Item
16) (see Photo 32)
. Crimp the female
disconnect
(Item 16)
onto the wire to
secure it
(see Photo 33)
.
Photo 32
Photo 33
16
14
16
Photo 31
NOTE: Exact location will vary
depending on your configuration.
Punch a mark on the panel through the
mounting hole on the timer
(see Photo
29)
. Drill a hole with a #20 drill bit at the
punch mark.
Screw the self tapping screw
(Item 15)
into the new hole to secure the timer to
the panel
(see Photo 30)
.
The delay timer
(Item 14)
will be installed
inline directly before the solenoid valve.
Remove the numbered power wire from
the correct solenoid valve (not the ground
or neutral; this wire should be a red wire)
(see Photo 31).
Many stations use wire
#4 for solenoid valve #1 and wire #6 for
solenoid valve #2, but consult your wiring
schematic for the correctly numbered wire
to remove.