MENTOR 12 US
SECTION 4 CONFIGURATION – Page 102
ER’S MANUAL
•
Time measurement:
You can choose for the time treatment, referring both to
its measurement and to the duration, to be directly in time units “seconds” or
in cycle numbers at the reference frequency, “Cycles”. Press on the desired
option to select.
•
Debounce:
The time parameter called “Debounce” refers to the behaviour
when detecting changes of state of the Binary Inputs, and it is defined as
the
time, after a change of state of a binary input, during which the
detection of new changes is inhibited.
The desired value is entered into
the respective window in
milliseconds
.
•
Glitch:
The time parameter called “Glitch” refers to the behaviour when
detecting changes of state of the Binary Inputs, and it is defined as
the time
that a level must remain for it to be considered a change.
The desired
value is entered into the respective window in
milliseconds.
•
Reference frequency:
This is the default frequency used for both buses. The
desired value is entered into the respective window in Hertz.
•
Language selection:
This is used to select the equipment work language.
When you press the button, a drop-down appears with the available language
options. Press on the one you wish to use.