MENTOR 12 USER’S MANUAL
SECTION 4: CONFIGURATION – Page 95
•
Normally Closed (NC)
: It assigns state 0 (deactivated) to it when the output
keeps its contact closed. State 1 (activated) corresponds to the open contact.
Usage Procedure
When you press on the tab marked “Binary Outputs” on the top of the screen that you
access when you press the CONFIGURATION option on the General Menu, you access
the configuration control screen of the Binary Outputs. This screen shows the current
configuration of the binary outputs and permits changing them.
As you can see in the figure, each binary output corresponds to a section that contains:
•
The order number of each input from OUT1 to OUT8.
•
A text window that, by means of the keypad (which appears on screen when
you touch this window), enables you to enter a specific name to identify each
output. This may be alphanumerical and may contain 5 characters at the
most.
•
Two cyclic operation buttons that permit selecting the binary output mode,
according to the above definitions.
All the outputs are independent and can be configured in any way without limitations.
When you finish configuring the outputs you do not need to confirm anything. The
outputs are configured as shown on the screen just by exiting it.