- 82 -
Drive ALM
(1-099)
C
RESET
input
<Contents>
A positioning operation or pushing operation is requested.
Before execute the return to origin position.
<Countermeasure>
Modify the setting so that those operations will be requested after
the return to origin position is completed.
ORIG Sens ALM
(1-103)
C
RESET
input
<Contents>
The origin sensor does not respond correctly when return to
origin operation is performed with the origin sensor. Alarm is
generated depending on the set value of the return to origin
parameter.
Return to origin parameter
setting
Alarm generating conditions
ORIG mode
ORIG sensor
1: Return to
origin by
pushing
force
0. No sensor
No alarm will be generated
1. Sensor
Contact A
The end position is detected when
the sensor has been OFF since the
return to origin operation started
2. Sensor
Contact B
The end position is detected when
the sensor has been ON since the
return to origin operation started
2,3. Return
to origin
with sensor
0. No sensor
Right after inputting a command of
return to origin.
1. Sensor
Contact A
Right after inputting a command of
return to origin, the end position is
detected when the sensor has been
OFF since the return to origin
operation started. Or the end
position is detected after the sensor
ON is detected and before the return
to origin operation is completed.
2. Sensor
Contact B
The end position is detected when
the sensor has been ON since the
return to origin operation started or
the end position is detected after the
sensor OFF is detected and before
the return to origin operation is
completed.
<Countermeasure>
- When ORIG mode is 1:
Set the return to origin sensor at
“0”.
- When ORIG mode is 2 or 3:
Set the return to origin sensor in accordance with the sensor
specifications. Also, check if the sensor mounting and the cable
connection of the sensor are correct.
AbEnc Comm ALM
(1-106)
C
RESET
SVON
input
<Contents>
The alarm is generated when the communication between the
controller circuit and the absolute circuit is not normal. (This
controller has not absolute function.)
<Countermeasure>
Make sure that the sensor type of the basic parameter is 1. After
the parameter is changed, it is necessary to reapply the power.