- 8 -
Output pressure
Output pressure of the product is sent.
0
1
BYTE
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
Bit
Output pressure
(16Bit)
Value
Monitoring of output pressure
The output pressure can be monitored by the PLC receiving the output data from the regulator
where the output pressure is 16-Bit.
<Relation between the output pressure value (16-Bit) and output pressure>
Output pressure
0x0000
0x02BC
Output pressure
0kPa
700kPa
(Ex.) When the output pressure is 700kPa, the set pressure value is 0x02BC.
Diagnostic information
This product can detect the device error by diagnostic Bit in the process data.
Byte
No.
Bit
No.
Item
Applicable
event
code
Details
4
Bit 15
Error
-
ON with any of Bits 11 to 14 of Byte 4
Set, otherwise 0.
Bit 14
Memory error
0x1810
Occurs on memory error.
Bit 13
System error
0x1811
Occurs when a system error .
Bit 12
Solenoid valve error
0x1812
Occurs when a solenoid valve error .
Bit 11
Internal
communication error
0x1813
Occurs when an internal communication error .
Bit 10
Alarm generation
-
Bit 8~9 of Byte 4 and Bit 7~4 of Byte 5
It is set when any of them is ON, otherwise it is 0.
Bit 9
Excessive power
supply voltage
0x5110
Occurs when the power supply voltage exceeds
the specification.
Bit 8
Low power supply
voltage
0x5111
Occurs when the power supply voltage is below
specification.
5
Bit 7
Excessive output
pressure
0x8C10
Occurs when the output pressure is exceeded.
Bit 6
Low output pressure
0x8C30
Occurs when the output pressure is too low.
Bit 5
Over target pressure
0x1820
Occurs when the target pressure exceeds the
specification range.
Bit 4
Residual pressure
error
0x1821
Occurs when performing zero clear while
residual pressure remains.
Bit 3
Accumulated
energizing time
reached
0x1830
Occurs when the accumulated time reaches the
set value.
Bit 2
Pressure setting error
notification
0x1831
Notifies you when the pressure setting is
abnormal.
Bit 1
Standby reached
-
Occurs when reaching standby mode.
Bit 0
SSC1
-
Occurs when the output pressure is within ±10%
F.S. of the target pressure.