- 14 -
Symbol
Data type
(IO-Link
standard)
Data length
Bit [BYTE]
Description
U8
UIntegerT
8 [1]
Unsigned integer (unsigned integer)
U16
16 [2]
U32
32 [4]
STR64
StringT
-
Up to 64-BYTE character string
(String)
* 3 “ Y” indicates that the parameter setting data is saved to the master, and “N" indicates that
the parameter is not saved.
Pressure setting method
This product switches the switching flag on the process data using the set value
(INDEX: 0x4A) of operation mode (PS1) and the set value (INDEX: 0x4B) of standby
mode (PS2). , It will adjust the pressure.
Values outside the specification range will be recognized as large values and cause
Er1, so please do not use them.
<
Relationship between the set pressure (16-Bit) and output pressure
>
Set pressure
0
x
0000
0x02BC
Output
pressure
0kPa
700kPa
(Example) When the set pressure value is 0x02BC, the output pressure is adjusted to 700kPa.
See page 9 for process data details.