- 19 -
Parameter index 0x4A
Parameter name Operation Mode (PS1)
Function
When the process data output switching flag (BIT 0 of BYTE0)
detects a Low (False) level, the mode transitions to operation
mode and the pressure is regulated to the value set by this
parameter.
Bit
Bit 15
~
0
(
2BYTE
)
Value
Adjustable from 0x0000 to 0x02BC.
0x0000=0kPa, 0x02BC=700kPa.
It is not linked with the display unit.
※
indicates the initial shipping value.
In addition, the program can be set up to 0×41A = 1050kPa.
Parameter
0x4B
Parameter
Standby Mode (PS2)
Function
When the process data output switching flag (BIT 0 of BYTE0)
detects the level of High (True), it transitions to standby mode and
the pressure is adjusted to the pressure set by this parameter.
Bit
Bit 15
~
0
(
2BYTE
)
Value
Adjustable from 0x0000 to 0x02BC.
0x0000=0kPa, 0x02BC=700kPa.
It is not linked with the display unit.
※
indicates the initial shipping value.
In addition, the program can be set up to 0×41A = 1050kPa.