- 31 -
Pressure Ramp Up Duration
Interlocked with the IO-Link parameter.
Set the time to reach the operation mode set
pressure when shifting to operation mode.
No
Key operation
LED Display
(1)
Deactivate the key lock if necessary (see page 22).
(2)
Press S-key for 2 seconds or more, then go to detail setting mode.
(3)
To "F07" by using the
△
and
▽
keys.
⇔
(displayed alternately)
(4)
Press S-key.
(5)
Set Pressure Ramp Up Duration by using
the
△
and
▽
keys.
(number changes)
※
Setting range : refer to Note 1
(6)
Press S-key.
⇔
(displayed alternately)
(7)
Press S-key for 2 seconds or more, then go out from detail setting mode.
(Select the menu with
△
or
▽
keys, then jump to another item.)
(8)
Activate the key lock if necessary (see page 22).
(
Note1
):
The setting range of Pressure Ramp Up Duration is 0 to 1500 (in units of 0.1 seconds).
The relationship between the LED display by key operation and Pressure Ramp Up Duration is
as follows.
LED
Pressure Ramp Up Duration
[sec]
0
0
1
0.1
F00
150
※
is the factory default value.
Only the third digit of the LED display is displayed in
hexadecimal.
Therefore, "F00" represents "1500" in decimal, and
the setting value is in units of 0.1 seconds.
Pressure Ramp Up Duration will be "150 seconds".
If Pressure Ramp Up Duration is 0 (factory default), the function is disabled.
※