- 20 -
Parameter index
0x4D
Parameter name
Set value of Solenoid Valve Stop Time
Function
This function reduces operation of the solenoid valves when the
supply pressure is insufficient.
Bit
Bit 7
~
0
(
1BYTE
)
Value
It can be set from 0% to 99% (of 100 seconds).
If the value is 0, the operating duration reduction is 0% and this
function is disabled. In the case of 99, the operating duration is
reduced by 99%.
※
The initial value is "0" and is disabled.
Parameter index
0x52
Parameter name
Pressure Ramp Up Duration setting
Function
This function gradually changes the command value in the set
time when shifting from power ON to operation mode, from
standby mode to operation mode or from isolation mode to
operation mode.
Even if the output pressure is higher than the set pressure during
the transition time of the set pressure, the exhaust operation will
Bit
Bit 15
~
0
(
2BYTE
)
Value
It can be set in units of 0.1 seconds from 0 to F00 (1500).
(1=0.1sec)
※
The initial value is "0" and is disabled.
※
indicates the initial shipping value.