![SMC Networks IP8001 Series Скачать руководство пользователя страница 53](http://html1.mh-extra.com/html/smc-networks/ip8001-series/ip8001-series_operation-manual_1301063053.webp)
No.IP8S-OM00009
52
<(760) User operation setting>
Line of 11 points curves defined by customer is set by operating
actuator position.
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to start
parameter change mode.
2
Select (USEr) with the UP or
DOWN button ( ) and hold
down the set button ( ) for
1sec. or longer.
3
Select (ACT) for value setting, and
hold down the set button ( )
for 1sec. or longer.
4
Hold down the set button ( )
for 1sec. or longer with specified
input current parameter.
5
The LCD displays go (Go) for
confirmation. Confirm there are no
hazardous conditions due to the
actuator startup, and then hold
down the set button ( ) for
1sec. or longer.
6
Operate the actuator by pressing
UP or DOWN button ( ).
Check the actuator movement, and
hold down the mode button ( ) at
desired position for 1sec.
7
Pressing UP or DWON button
( ), and set input current
parameter of 10 points as clause 4
to 6.
8
Hold down the mode button ( )
again for 1sec. or longer for 3 times
with some interval.
or
+
or
+
+
+
+
or
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...