No.IP8S-OM00009
25
If hunting occurs during step 3 (StP3) through step 5 (Stp5)
and a check code (CHE0001 or CHE0003) is displayed,
perform readjustment in the following manner.
<When a check code 1 (CHE0001) is displayed>
Procedure
LCD display
1
If
hunching
occurs
during
adjustment, the PID constant is
adjusted to automatically eliminate
it.
2
After hunting has been eliminated,
automatically check the balance
current.
3
If good (Good) is displayed and all
steps are not completed, move onto
the next step. When step 5 (StP5) is
completed,
a
check
code
1(CHE0001) will be displayed. If
there are no steps left, the check
code 1 (CHE0001) will be displayed
3 seconds after
*14
.
14: Perform adjustments while referring to the check code list.
<When a check code 3 (CHE0003) is displayed>
Procedure
LCD display
1
If hunting that is too small to be
detected by a hunting attenuation
program occurs during adjustment,
calibration
will
be
stopped
automatically.
2
A check code 3 (CHE0003) is
displayed
*15
.
15: When hunting that is too small to be detected by a hunting
attenuation program occurs, the P constant will go over the
appropriate value. Reduce it manually. For details, refer to the
applicable countermeasure in ”
■
Check Code List”.
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...