No.IP8S-OM00009
26
5. Input current calibration
Normally, input current dose not need to be calibrated. If input
values (S value) have a displacement in auto mode after the
above adjustment, input current of 4 to 20mADC can be
calibrated.
Procedure
LCD display
1
Press the UP or DOWN button
( ) in calibration mode to
select signal-zero (S-0).
2
Apply an input current of 4mA DC
and hold down the set button
( ) for 1sec. or longer.
3
The LCD displays go (Go) for
confirmation.
To
implement
calibration, hold down the set
button ( ) for 1sec. or longer
again.
4
The LCD continues to display bars
(----) during calibration.
5
The LCD displays pass (PASS)
after calibrating the input current
has been completed, and the
calibration (CAL) mode selection
screen returns automatically.
6
Press the UP or DOWN button
( ) in calibration mode and
select signal-finish (S-F).
7
Apply an input current of 20mA DC
and hold down the set button
( ) for 1sec. or longer.
8
The LCD displays go (Go) for
confirmation.
To
implement
calibration, hold down the set
button ( ) for 1sec. or longer
again.
9
The LCD continues to display bars
(----) during calibration.
10
The LCD displays pass (PASS)
after the input current has been
completed, and the calibration
(CAL)
mode
selection
screen
returns automatically.
+
or
+
or
+
+
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...