No.IP8S-OM00009
73
■
Parameter Setting Default Value List
Table 14 shows parameter default value at ex-factory. See table below to return some parameters to
default value after repeating setting and change. All parameters can be returned to default value by
performing Initialize (C80). After initialize (C80), initial adjustment is necessary.
Table14
Parameter
Set items
Parameter item
Details
Setting
assigned
Status
Set
value 1
Set
value 2
Parameter
item
(000) Actuator type
-
Not
changeable
-
-
-
-
(200) Operating direction
-
-
dir
-
-
-
(300) Split range setting
-
oFF
-
0.0
100.0
-
(400) Zero-span setting
-
oFF
-
-
-
-
VALU, ACt
-
-
0.0
100.0
-
rAtE
-
-
100.0
100.0
100
(500) Forced fully-close /
fully-open
(Both
close/open)
on
-
0.5
99.5
-
(600) Dead band
-
-
-
0.0
-
-
(700) Valve opening
characteristic setting
-
-
Lin
-
-
-
VALU, ACt
-
-
0.0
-
-
(User set value)
-
-
1.0
-
-
-
-
4.0
-
-
-
-
9.0
-
-
-
-
16.0
-
-
-
-
25.0
-
-
-
-
36.0
-
-
-
-
49.0
-
-
-
-
64.0
-
-
-
-
81.0
-
-
-
-
100.0
-
-
(800) PID constant setting
Proportional
gain
(P constant)
-
-
1.000
-
-
Integral time
(I constant)
-
-
0.250
-
-
Differential time
(D constant)
-
-
0.250
-
-
Easy
adjustment
(All constant)
-
-
0
-
-
(900) Alarm 1 setting
-
OFF
-
0
-
-
(A00) Alarm 2 setting
-
OFF
-
100
-
-
(b00) Analog output
setting
-
-
inC
-
-
-
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...