No.IP8S-OM00009
63
(b00) Analog output setting
(C00) Calibration
<(C10) Check angle of
feedback lever
*22
>
<(C20) Simple balance current
adjustment
*23
>
<(C30) Calibration
*24
>
Possible to check the feedback lever angle, balance current
adjustment, zero/span adjustment, input current adjustment,
parameter initialize.
The angle of the feedback lever unit connected to the valve stem is
checked.
22:
For adjustment procedure, see “(2) Check the angle of the feedback
lever” of “
■
Initial A
djustment”.
Adjust the balance current of the torque motor.
23:
For adjustment procedure, see “(3)Simple balance current
adjustment” of “
■
Initial Adj
ustment”.
Adjust zero-span and PID constant automatically.
24:
For adjustment procedure, see “4.Calibration” of “
■
Initial
A
djustment”.
Possible to select analog output proportional output (inC) and
reversed output (dEC).
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to start
parameter change mode.
2
Select proportional output (inC) or
reversed output (dEC) by UP or
DOWN button
(
)
.
3
Hold down the mode button ( ) for
1sec. or longer to set output mode.
+
or
Proportional output
Reversed output
Mode button
(
)
≧
1s
Set button
+
(
)
≧
1s
or
Fig. 44
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...