No.IP8S-OM00009
10
Mounting
1. Confirm the positioner is securely and firmly mounted onto the actuator.
2. Be careful not to get a finger caught when matching mounting positions.
1. Be sure to keep the necessary space available for maintenance work (piping, wiring,
adjustment, etc.) in your setup location.
2. Cut off the pressure supply to ensure compressed air is discharged from the positioner
and actuator completely before starting mounting.
3. When removing the positioner from the actuator and mounting it onto another actuator,
malfunctions may occur due to its remained initial constant. When the positioner is transferred
onto another actuator, apply input current, initialize the parameters in the calibration mode,
(parameter code: C80) and perform initial adjustments before supplying air.
■
Example of Mounting on Actuator
IP8001 Smart Positioner offers interchangeability in mounting pitch with the IP600, IP6000 and
IP8000 Positioners. Therefore, it is possible to apply a bracket for IP600, IP6000 and IP8000 for
mounting
*1
.
1: There is a possibility that the connection and the feedback lever interfere when the IP600 type is
exchanged for the IP8001 type. Please machine the connection or interpose the spacer between the
positioner and the bracket at that time.
Warning
!
Caution
!
Attach using the screw hole at a
side of the positioner and the
screw hole at the front mount of
diaphragm valve.
Attach using the screw hole at
the positioner back and the
screw hole at the front mount
of diaphragm valve.
Fig. 4
Directly attach using the screw
hole at a side of the positioner
and the screw hole at the yoke
side of diaphragm.
Fig. 6
Fig. 5
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...