No.IP8S-OM00009
35
(700) Valve opening
characteristics setting
Valve opening characteristic can be selected from the following.
(700) = Lin Linear
Y=X
(710) = EP25 Equal percentage 1:25 (R=25)
Y=(R
X-1
-0.04)×1/0.96
(720) = EP50 Equal percentage 1:50 (R=50)
Y=(R
X-1
-0.02)×1/0.98
(730) = qo25 Quick opening 25:1 (R=25)
Y=(1-R
-X
)×1/0.96
(740) = qo50 Quick opening 50:1 (R=50)
Y=(1-R
-X
)×1/0.98
(750) = USEr
User’s definition
〔
11 polygonal line settings
〕
The default value at shipping is (700) = (Lin) Linear. When u
ser’s
definition (USEr) is set, the following 11 data can be set
*7
.
However, the setting range is between -20.0 and 120.0%.
Definition by user can be set by value (vALU) and operation (ACt).
(750,760) Input current 0% position = 0.0% (Default value)
(751,761)
〃
10% position = 1.0% (
〃
)
(752,762)
〃
20% position = 4.0% (
〃
)
(753,763)
〃
30% position = 9.0% (
〃
)
(754,764)
〃
40% position = 16.0% (
〃
)
(755,765)
〃
50% position = 25.0% (
〃
)
(756,766)
〃
60% position = 36.0% (
〃
)
(757,767)
〃
70% position = 49.0% (
〃
)
(758,768)
〃
80% position = 64.0% (
〃
)
(759,769)
〃
90% position = 81.0% (
〃
)
(75A,76A)
〃
100% position = 100.0% (
〃
)
0
100
0
100
100%
Fig. 30
7: Be sure to set all 11 date items. To use forced fully-close / fully-open
(parameter code: 500), set items so that stroke (Y) increases
according to input current (X) increases.
Linear
Quick opening 50
%
Input current (X)
S
tr
ok
e (Y)
0%
100%
Equal
percentage 50
%
User
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...