No.IP8S-OM00009
21
Supply
pressure gauge
OUT1
pressure gauge
6: Auto and manual mode can be switched by rotating the pilot valve
unit auto/manual switch screw to the manual (M) side as shown in
Fig. 17. A small stopper screw in the top is to prevent loosening and
must not be tampered with or loosened. Also, a sensitivity holding
screw is set prior to factory shipment and must not be accidentally
rotated.
Fig. 16
4: The positioner standard stroke is a rotational angle of 10 to 30
o
. An
Installations condition with a rotating angle of less than 10
o
or over
30
o
is not available.
5: A Description of pressure gauges mounted on the positioner are as
shown in Fig. 16.
Auto/manual
switch screw
(Built-in fixed orifice)
Stopper screw
(Do not move)
Fig. 17
Looseness
prevention
marking
Sensitivity holding screw
(Do not move)
- Be sure to normally tighten
the screw to the auto side
(A) when the positioner is
operated
with
an
input
current.
- Supply pressure and the
OUT1 output are connected
by rotating the Auto/Manual
changeover screw towards
M.
Manual stroke adjustment
of the diaphragm valve and
single acting actuator can be
adjusted by using the supply
pressure
setting
reducing
valve
Mode
switching
is
available by approx. 1/8 turn.
Keep the rotation within 1/4 to
1/8 turn.
B
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...