No.IP8S-OM00009
42
■
Parameter Setting Procedure
(000) Actuator type
(200) Operation direction
setting
(300) Split range setting
This parameter is fixed when shipped out of the factory. User can
not change it.
Possible to select split range mode (on), non split range mode
(oFF), and set values when split range mode is selected.
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to enter the
parameter change mode.
2
Select split range mode (on) or non
split range mode (oFF) with UP or
DOWN button ( ).
3
When split range mode (on) is
selected, enter the value change
mode with the set button ( ).
When non split range mode (oFF)
is selected, hold down the mode
button ( ) to settle the mode.
+
or
+
Customer can select direct (dir) or reverse (rvs).
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to enter the
parameter change mode.
2
Select direct operation (dir) or
reversed operation (rvs) by DOWN
or UP button ( ).
3
Hold down the mode button ( ) for
1sec. or longer.
+
or
Fig. 35
or
Reverse direction
Direct direction
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s