(500) Forced fully-close/
fully-open setting
Fig. 37-4
When forced fully-close / fully-open (on) is selected, set value can
be changed.
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to move on to
parameter change mode.
2
Press the UP or DOWN button
( ) to select (510), and hold
down the set button ( ) for
1sec. or longer.
3
Select (on) or (oFF) with UP or
DOWN button ( ).
4
<
Hereafter, only when (on) is set
>
For setting the lower value with
(510), hold down the set button
( ) for 1sec. or longer for 2
times with some interval. A
fter
values start flashing,
change the
value within the range of 0.0 to
10%. After changing, hold down the
mode button ( ) for 1 sec. or
longer for 3 times with some
interval.
+
or
+
+
or
Set button
+
(
)
≧
1s
C
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
or
or
Span setting
failure
Set button
+
(
)
≧
1s
Mode button
(
)
≧
1s
Set button
+
(
)
≧
1s
Mode button
(
)
≧
1s
Mode
button
( )
≧
1s
Mode
button
( )
≧
1s
Set button
+
(
)
≧
1s
Set button
+
(
)
≧
1s
Upper limit setting
(
%
)
Lower limit setting
(
%
)