![SMC Networks IP8001 Series Скачать руководство пользователя страница 51](http://html1.mh-extra.com/html/smc-networks/ip8001-series/ip8001-series_operation-manual_1301063051.webp)
No.IP8S-OM00009
50
(600) Dead band setting
(700) Valve opening
characteristics setting
<(710
~
740) Selection setting>
Set dead band (d-b).
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to start
parameter change mode.
2
Hold down the set button ( )
for 1sec. or longer.
After values
start flashing, change the value
within the range of 0.0 to 10.0%.
After changing, hold down the
mode button ( ) for 1sec. or longer
to set the value.
3
Hold down the mode button ( )
again for 1sec. or longer to set the
mode.
+
+
Valve opening characteristic can be set. The characteristic is
plotted by 11 points as specified by user.
Selected from 5 representative valve open degree characteristic.
Procedure
LCD display
1
Hold down the set button ( )
for 1sec. or longer to start
parameter change mode.
2
Select from the following by UP or
DOWN button ( ).
- Linear (Lin)
- Equal percent 25 (EP25)
- Equal percent 50 (EP50)
- Quick opening 25 (qO25)
- Quick opening 50 (qO50)
3
Hold down the mode button ( )
again for 1sec. or longer to set the
mode.
or
+
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Mode button
(
)
≧
1s
Set button
+
( )
≧
1s
Dead band setting
Fig. 39
Содержание IP8001 Series
Страница 1: ...No IP8S OM00009 B SMART POSITIONER LEVER TYPE PRODUCT NAME IP8001 Series MODEL Series...
Страница 14: ...No IP8S OM00009 13 Table 7 Piping Layout...
Страница 85: ...No IP8S OM00009 84 Drawing...
Страница 86: ...No IP8S OM00009 85...
Страница 87: ...No IP8S OM00009 86...
Страница 88: ...No IP8S OM00009 87...