HRX-OM-W002-A
Chapter 8
Control, Inspection, Exchange and Cleaning
8.2
Inspection, exchange, cleaning
HRR Series
8-8
8.2.4
Inspection every 6 months
Check for water leakage from pump (For option T [High head pump])
Remove the filter panel and check the pump for excessive leakage. If the
leakage is found, replace the mechanical seal.
Fig. 8.2-4 leak check
Pump
Circulating fluid should not be
accumulating in drain pan.
Leakage from the mechanical seal
It is impossible to prevent the leakage from the mechanical seal completely because
of its structure. Although the leakage is described as 3cc/hr or less.
The recommend life time of the mechanical seal before needing replacement is 6000
to 8000 hours (usually 1 year)
Содержание HRR012-A*-20 Series
Страница 14: ...HRX OM W002 A Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 110: ...HRX OM W002 A Chapter 5 Display and Setting of Various Functions 5 5 Advanced setting mode HRR Series 5 62...
Страница 138: ...HRX OM W002 A Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 18...
Страница 156: ...HRX OM W002 A Chapter 9 Documents 9 9 Daily Check HRR Series 9 18...
Страница 159: ......