5.5 Advanced setting mode
5-39
Ambient temperature lower limit alarm
17.
Press the [▼] key. Displays screen for setting the lower limit of the ambient
temperature alarm.
Displayed for air-cooled type only. (This item is not displayed for water-cooled type)
Lower limit of alarm AL11: Ambient temperature alarm can be changed.
●Setting range: 5.0 to 40.0
℃
(initial value: 10.0
℃
)
Switching of the leakage alarm
18.
Press the [▼] key. Displays screen for setting the leakage alarm operation.
Operation for alarm AL04: Leakage alarm can be selected.
Set value
Contents
Initial value
OFF
Alarm is not generated.
―
WRN
Operation of this product will continue when the
alarm occurs.
○
FLT
Operation of this product will stop when the alarm
Occurs.
―
Switching of the contact input signal 1
19.
Press the [▼] key. Displays screen for setting the operation of the Contact input signal
1.
Operation for alarm AL25: Contact input signal 1 detection can be selected.
Set value
Contents
Initial value
OFF
Alarm is not generated.
―
WRN
Operation of this product will continue when the alarm
occurs.
―
FLT
Operation of this product will stop when the alarm occurs.
○
RUN
℃
AMB
⇒
LOTMP
(
Alternately displayed
)
RUN
Operation of leakage alarm
Operation of the contact input signal 1
INP1
⇒
ALARM
(
Alternately displayed
)
WATER
⇒
LERK
⇒
ALARM
(
Alternately displayed
)
Ambient temperature lower limit alarm
Содержание HRR012-A*-20 Series
Страница 14: ...HRX OM W002 A Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 110: ...HRX OM W002 A Chapter 5 Display and Setting of Various Functions 5 5 Advanced setting mode HRR Series 5 62...
Страница 138: ...HRX OM W002 A Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 18...
Страница 156: ...HRX OM W002 A Chapter 9 Documents 9 9 Daily Check HRR Series 9 18...
Страница 159: ......