HRX-OM-W002-A
Chapter 2 Name and Function of Parts
HRR Series
2.3 Function of Parts
2-5
2.3 Function of Parts
The function of parts is as follows
Table 2-3
Function of parts
Name
Name
Operation display panel
Runs and stops the product and performs settings such as the circulating
fluid temperature.
For details, refer to
’’.
Fluid level gauge
Indicates the circulating fluid level of the tank. For details, refer to
’’.
Power supply switch
Shuts off the power supply to the internal eqipment of product.
Model label
Shows the part number of the product.
For details, refer to
’’.
Circulating fluid outlet port
The circulating fluid flows out from the outlet port.
Circulating fluid return port
The circulating fluid returns to the return port.
Drain port
Port to drain the circulating fluid out of the tank.
Power supply connector
Connect the power cable to the Power supply connector
accessory, and then plug it in.
For details, refer to " 3.3.3
Preparation and wiring of power supply cable
".
Communication connector
CN1,CN2
Use for contact input / output, serial communication.
For details, refer to "3.3.3
Preparation and wiring of power supply
Facility water inlet
(For water-cooled type)
A facility water inlet to which the facility water is fed through piping.
The pressure of facility water should be in a range of 0.3 to 0.5MPa.
Facility water outlet
(For water-cooled type)
A facility water out
let from which the facility water returns to the user’s
machine through piping.
Содержание HRR012-A*-20 Series
Страница 14: ...HRX OM W002 A Chapter 1 Safety Instructions 1 8 Material Safety Data Sheet MSDS HRR Series 1 8...
Страница 110: ...HRX OM W002 A Chapter 5 Display and Setting of Various Functions 5 5 Advanced setting mode HRR Series 5 62...
Страница 138: ...HRX OM W002 A Chapter 8 Control Inspection Exchange and Cleaning 8 5 Electrical schematic diagram HRR Series 8 18...
Страница 156: ...HRX OM W002 A Chapter 9 Documents 9 9 Daily Check HRR Series 9 18...
Страница 159: ......