HRX-OM-W002-A
Chapter 3 Transport and Setting Up
HRR Series
3.2 Installation
3-5
Required facility water system (for water cooled type)
Table
3-2
Facility water source to be prepared
Model
Heat
Radiated
kW
Facility water temp.
range
o
C
Required facility water flow rate
l/min
Facility water temprature
25
℃
32
℃
40
℃
HRR012-W
-20-
Approx.2
5
to
40
(Rating 25)
8
12
20
HRR018-W
-20-
Approx.4
12
15
23
HRR024-W
-20-
Approx.5
14
17
25
HRR030-W
-20-
Approx.6
15
18
26
The water cooled product radiates heat to the facility water.
It is necessary to supply the facility water. Please prepare the facility
water system that satisfies the heat radiation and the facility water
specifications below.